HTML has links - PDF has Authentication
246-291-200  <<  246-291-205 >>   246-291-210

PDFWAC 246-291-205

Drinking water materials and additives.

(1) In the design of a new or expanding Group B system, all materials in contact with potable water shall conform to the ANSI/NSF Standard 61.
(2) Pipes, pipe fittings, fittings, fixtures, solder, or flux used in the design of a new or expanding Group B system shall be lead-free. For the purposes of this section, lead-free means:
(a) Not more than a weighted average of twenty-five one-hundredths of one percent lead for wetted surfaces of pipes and pipe fittings; and
(b) No more than two-tenths of one percent lead in solder and flux.
(3) Any chemicals specified for use in the design of treatment for secondary MCLs in Table 3 under WAC 246-291-170, with the exception of unscented commercial grade hypochlorite compounds, shall comply with ANSI/NSF Standard 60. The design dosage shall not exceed the maximum application dosage recommended for the product as certified by the ANSI/NSF Standard 60.
(4) The department may review and approve the use of materials or additives that are not ANSI/NSF Standard 60 or 61 certified on a case-by-case basis.
[Statutory Authority: RCW 43.20.050 and chapter 70.119A RCW. WSR 12-24-070, ยง 246-291-205, filed 12/4/12, effective 1/1/14.]