HTML has links - PDF has Authentication
51-11C-403323  <<  51-11C-403324 >>   51-11C-403325

PDFWAC 51-11C-403324

Table C403.3.2(4)Minimum efficiency requirementsElectrically operated PTAC, PTHP, SPVAC, SPVHP, room air conditioners.

Table C403.3.2(4)
Electrically Operated Packaged Terminal Air Conditioners, Packaged Terminal Heat Pumps, Single-Package Vertical Air Conditioners, Single-Package Vertical Heat Pumps, Room Air Conditioners and Room Air-Conditioner Heat PumpsMinimum Efficiency Requirementse
Equipment Type
Size Category (Input)
Subcategory or Rating Condition
Minimum Efficiency
Test Procedurea
PTAC (cooling mode) Standard size
< 7,000 Btu/h
95°F db/75°F wb outdoor airc
11.9 EER
AHRI 310/380
≥ 7,000 Btu/h and ≤ 15,000 Btu/h
14.0 - (0.300 × Cap/1000) EERd
> 15,000 Btu/h
9.5 EER
PTAC (cooling mode) Nonstandard sizea
< 7,000 Btu/h
95°F db/75°F wb outdoor airc
9.4 EER
AHRI 310/380
≥ 7,000 Btu/h and ≤ 15,000 Btu/h
10.9 - (0.213 × Cap/1000) EERd
> 15,000 Btu/h
7.7 EER
PTHP (cooling mode) Standard size
< 7,000 Btu/h
95°F db/75°F wb outdoor airc
11.9 EER
AHRI 310/380
≥ 7,000 Btu/h and ≤ 15,000 Btu/h
14.0 - (0.300 × Cap/1000) EERd
> 15,000 Btu/h
9.5 EER
PTHP (cooling mode) Nonstandard sizeb
< 7,000 Btu/h
95°F db/75°F wb outdoor airc
9.3 EER
AHRI 310/380
≥ 7,000 Btu/h and ≤ 15,000 Btu/h
10.8 - (0.213 × Cap/1000) EERd
> 15,000 Btu/h
7.6 EER
PTHP (heating mode) Standard size
< 7,000 Btu/h
47°F db/43°F wb outdoor air
3.3 COPH
AHRI 310/380
≥ 7,000 Btu/h and ≤ 15,000 Btu/h
3.7 - (0.052 × Cap/1000) COPHd
> 15,000 Btu/h
2.90 COPH
PTHP (heating mode) Nonstandard sizeb
< 7,000 Btu/h
47°F db/43°F wb outdoor air
2.7 COPH
AHRI 310/380
≥ 7,000 Btu/h and ≤ 15,000 Btu/h
2.9 - (0.026 × Cap/1000) COPHd
> 15,000 Btu/h
2.5 COPH
SPVAC (cooling mode)
< 65,000 Btu/h
95°F db/75°F wb outdoor airc
11.0 EER
AHRI 390
≥ 65,000 Btu/h and
< 135,000 Btu/h
10.0 EER
≥ 135,000 Btu/h and
< 240,000 Btu/h
10.0 EER
SPVHP (cooling mode)
< 65,000 Btu/h
95°F db/75°F wb outdoor airc
11.0 EER
AHRI 390
≥ 65,000 Btu/h and
< 135,000 Btu/h
10.0 EER
≥ 135,000 Btu/h and
< 240,000 Btu/h
10.0 EER
SPVHP (heating mode)
<65,000 Btu/h
47°F db/43°F wb outdoor air
3.3 COP
AHRI 390
≥ 65,000 Btu/h and
< 135,000 Btu/h
3.0 COP
≥ 135,000 Btu/h and
< 240,000 Btu/h
3.0 COP
Room air conditioners without reverse cycle with louvered sides for applications outside U.S.
< 6,000 Btu/h
-
11.0 CEER
ANSI/AHAMRAC-1
≥ 6,000 Btu/h and
< 8,000 Btu/h
-
11.0 CEER
≥ 8,000 Btu/h and
< 14,000 Btu/h
-
10.9 CEER
≥ 14,000 Btu/h and
< 20,000 Btu/h
-
10.7 CEER
≥ 20,000 Btu/h and
< 28,000 Btu/h
-
9.4 CEER
≥ 28,000 Btu/h
-
9.0 CEER
Room air conditioners without louvered sides
< 6,000 Btu/h
-
10.0 CEER
ANSI/AHAMRAC-1
≥ 6,000 Btu/h and
< 8,000 Btu/h
-
10.0 CEER
≥ 8,000 Btu/h and
< 11,000 Btu/h
-
9.6 CEER
≥ 11,000 Btu/h and
< 14,000 Btu/h
-
9.5 CEER
≥ 14,000 Btu/h and < 20,000 Btu/h
-
9.3 CEER
≥ 20,000 Btu/h
-
9.4 CEER
Room air conditioners with reverse cycle, with louvered sides for applications outside U.S.
< 20,000 Btu/h
-
9.8 CEER
ANSI/AHAMRAC-1
≥ 20,000 Btu/h
-
9.3 CEER
Room air conditioners with reverse cycle without louvered sides for applications outside U.S.
< 14,000 Btu/h
-
9.3 CEER
ANSI/AHAMRAC-1
≥ 14,000 Btu/h
-
8.7 CEER
Room air conditioners, casement only for applications outside U.S.
All capacities
-
9.5 CEER
ANSI/AHAMRAC-1
Room air conditioners, casement-slider for application outside U.S.
All capacities
-
10.4 CEER
ANSI/AHAMRAC-1
For SI: 1 British thermal unit per hour = 0.2931 W, °C = [(°F) - 32]/1.8.
 
 
"Cap" = The rated cooling capacity of the product in Btu/h. If the unit's capacity is less than 7,000 Btu/h, use 7,000 Btu/h in the calculation. If the unit's capacity is greater than 15,000 Btu/h, use 15,000 Btu/h in the calculations.
 
a
Chapter 6 contains a complete specification of the referenced standards, which include test procedures, including the referenced year version of the test procedure.
 
b
Nonstandard size units must be factory labeled as follows: "MANUFACTURED FOR NONSTANDARD SIZE APPLICATIONS ONLY: NOT TO BE INSTALLED IN NEW STANDARD PROJECTS." Nonstandard size efficiencies apply only to units being installed in existing sleeves having an external wall opening of less than 16 inches (406 mm) high or less than 42 inches (1067 mm) wide and having a cross-sectional area less than 670 square inches (0.43 m2).
 
c
The cooling-mode wet bulb temperature requirement only applies for units that reject condensate to the condenser coil.
 
d
"Cap" in EER and COPH equations for PTACs and PTHPs means cooling capacity in Btu/h at 95°F outdoor dry-bulb temperature.
 
e
This table is a replica of ASHRAE 90.1 Table 6.8.1-4 Electrically Operated Packaged Terminal Air Conditioners, Packaged Terminal Heat Pumps, Single-Package Vertical Air Conditioners, Single-Package Vertical Heat Pumps, Room Air Conditioners, and Room Air-Conditioner Heat PumpsMinimum Efficiency Requirements.
[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapters 19.27A and 19.27 RCW. WSR 22-14-091, 23-12-101, and 23-20-021, § 51-11C-403324, filed 7/1/22, 6/7/23, and 9/25/23, effective 3/15/24.]