HTML has links - PDF has Authentication
194-50-070  <<  194-50-080 >>   194-50-090

PDFWAC 194-50-080

ASHRAE Standard 100, 2018Section 8Energy Audit Requirements.

8.1 The qualified energy auditor shall complete Form D and submit to the authority having jurisdiction (AHJ). If an energy audit is required within this section, a copy of the audit summary results shall be included in the compliance documentation in a format specified in Normative Annex Z. Compliance with this standard shall be achieved by adopting energy efficiency measures (EEMs) that collectively will reduce annual building energy use.
Exception to 8.1: For Level 1 audit, no Form D is required unless complying through conditional compliance or the decarbonization plan exception to Section W3.1.1(1).
8.2 Energy audit requirements for buildings without energy targets.
8.2.1 Overall process. A Level 2 energy audit (as defined in Section 8.4.2) shall be conducted for all Tier 1 covered buildings not having an energy target. The energy audit and the associated energy audit report shall be completed by a qualified energy auditor practicing within their field of competency.
Exception to 8.2.1:Buildings may use energy audits completed within five years prior to the building's compliance date, provided that the scope of the energy audit meets the requirements of this section and that there have been minimal changes to the systems within the audit scope. The energy audit must be evaluated consistent with the investment criteria in Normative Annex X.
8.2.2 The scope of the energy audit shall include the following required end uses as applicable to the building:
• Envelope;
• Lighting;
• Cooling;
• Heating;
• Ventilation and exhaust systems;
• Air distribution systems;
• Heating, chilled, condenser, and domestic water systems;
• Refrigeration except for food processing refrigeration;
• Power generation equipment;
• Uninterruptible power supplies and power distribution units;
• People-moving systems;
• The scope of the energy audit may include campus district heating and/or cooling systems when the campus district heating and/or cooling system serves the building being audited.
8.3.2 Buildings that do not meet their energy targets overall process. An energy audit shall be conducted, and an associated energy audit report shall be provided, for all buildings that do not meet their energy target. The energy audit shall be completed by a qualified energy auditor practicing within their field of competency. The energy audit shall be at an audit level specified by the qualified energy auditor to be sufficient to identify and evaluate the EEMs that, if implemented, would result in the building meeting its energy target. The qualified energy auditor may refer to the list of potential EEMs in Informative Annex E.
After the completion of the audit and the selection of EEMs to be implemented, the applicant must calculate an adjusted energy use intensity (EUI) for the building based on the estimated energy savings from the selected EEMs and the historical energy use of the building. This adjusted EUI is then compared to the energy target for the building. If the adjusted EUI is less than the energy target, the applicant shall proceed with implementation as specified in Section 9. If the adjusted EUI is greater than the energy target, a more rigorous energy audit investigation is required to identify additional EEMs. This process is repeated until the building's adjusted EUI is less than its energy target.
Calculation of the adjusted EUI is shown in the following equation:
EUIadj
=
(Energyhist- Energysaved)/GFA
Where:
 
 
Energyhist
=
Historical annual energy use, kBtu
Energysaved
=
Estimated annual energy savings, kBtu
GFA
=
Gross floor area, ft2
Following the completion of an energy audit that has identified EEMs sufficient to meet the building's energy target, the applicant shall implement those EEMs per the requirements of Section 9.
Exception to 8.3.2:Buildings may use energy audits completed within five years prior to the building's compliance date, provided that the scope of the energy audit meets the requirements of this section and there have been minimal changes to the systems within the audit scope. In this case, the same comparison of adjusted EUI to energy target shall be made by the applicant. If the EEMs identified in the audit are still applicable, have not been implemented, and if implemented would result in the building meeting its energy target, these measures shall be implemented by the facility, and the project shall follow the procedures in Section 9. If the identified EEMs do not result in an adjusted EUI less than the energy target, a new energy audit shall be conducted as described in Section 8.3.2.
8.4.1 Level 1 Audit.Buildings shall perform a Level 1 audit (walk-through analysis) as defined in ANSI/ASHRAE/ACCA Standard 211-2018 Standard for Commercial Building Energy Audits, Section 5.312.
8.4.2 Level 2 Audit.Buildings shall perform a Level 2 Audit (energy survey and engineering analysis) as defined in ANSI/ASHRAE/ACCA Standard 211-2018 Standard for Commercial Building Energy Audits, Section 5.412.
8.5.1 Audit results. The energy audit report shall define the actions necessary for the building owner to achieve the energy and cost savings that are recommended in the report.
Energy audit results shall be presented in a summary table that includes, at a minimum, an estimate of each of the following:
• A list of recommended EEMs that, if implemented, will either meet the energy target for the building if it has a target or, if it does not have an energy target, will meet the economic criteria set by the standard in Section 9.
• The estimated energy savings and peak demand savings associated with each recommended EEM, expressed in the cost units used on the building owner's energy bills, and the units used for comparison with the energy target.
• The estimated (modeled) energy cost savings associated with each recommended EEM.
• The estimated cost of implementation for each recommended EEM. The costs of implementation shall include the required monitoring of energy savings per the requirements of Section 9.
The economic evaluation of measures are required by Normative Annex X.
8.5.2 Interactive effects. Energy savings analysis shall include interactive effects of all selected EEMs. When considering multiple EEMs with interactive effects, the order of analysis shall start with load reduction measures and proceed through distribution systems and associated equipment efficiencies and then plant and heat-rejection systems. Any interactive effects on equipment sizing and part load performance of equipment shall be accounted for due to reduced loads on subsequent systems.
8.5.4.1 Nonfederal facilities. The minimum financial criteria required for reporting is specified in Normative Annex X.
8.5.4.2 U.S. Federal Facilities - Not adopted.
8.5.5 End-use analysis. The energy audit shall include an end-use analysis that compares the estimated energy use of the facility after implementation of all selected EEMs to historical utility consumption. The intent of this requirement is to ensure that estimates of the base-case end-use energy estimates and potential energy-savings estimates in the energy audit report are reasonable.
Informative Note: For example, if the audit identifies lighting retrofit opportunities, the qualified energy auditor shall compare the identified energy savings for those opportunities with the base-case energy use of the facility and demonstrate that they make up a reasonable fraction of the historical electricity consumption at the site.
8.5.5.2 Requirements for Level 2 Audits. The qualified energy auditor is required to estimate the energy use of all end uses that individually comprise more than five percent of total historical building energy use. The energy estimates for these end uses shall be summed and compared to historical energy consumption for the facility. The sum of the base-case end-use energy estimates must be between 90 percent and 100 percent of the historical energy use at the site.
This comparison shall be conducted separately for each fuel type, such as electricity, natural gas, or fuel oil, for which EEMs are identified. On-site energy sources such as solar, photovoltaic, geothermal, and wind shall be included.
Correction for historical weather for the base year versus average weather used in baseline estimates may be used.
The same energy use estimates that comprise the end-use analysis shall also be used as the basis for energy savings calculations. The qualified energy auditor shall verify that each EEM savings estimate is reasonable in comparison to the historical energy consumption of that end use based on energy consumption survey data or experience with similar sites.
The qualified energy auditor shall verify that the combined savings from multiple EEMs shall take into account interactive effects among measures.
Miscellaneous plug loads may be estimated on average equipment power density and building area. (See Form D in Normative Annex Z.)
[Statutory Authority: RCW 19.27A.210. WSR 24-16-041, § 194-50-080, filed 7/30/24, effective 8/30/24. Statutory Authority: RCW 19.27A.210 and 19.27A.250. WSR 24-03-033, § 194-50-080, filed 1/8/24, effective 2/8/24. Statutory Authority: RCW 19.27A.210. WSR 20-22-059, § 194-50-080, filed 10/30/20, effective 11/30/20.]