HTML has links - PDF has Authentication
51-51-2439  <<  51-51-2904 >>   51-51-4400

PDFWAC 51-51-2904

Section 2904Dwelling unit fire-sprinkler systems.

P2904.1.1 Required sprinkler locations. Sprinklers shall be installed to protect all areas of a dwelling unit.
EXCEPTIONS:
1. Uninhabitable attics, crawl spaces and normally unoccupied concealed spaces that do not contain fuel-fired appliances do not require sprinklers. In uninhabitable attics, crawl spaces and normally unoccupied concealed spaces that contain fuel-fired equipment, a sprinkler shall be installed above the equipment; however, sprinklers shall not be required in the remainder of the space.
 
2. Clothes closets, linen closets and pantries not exceeding 24 square feet (2.2 m2) in area, with the smallest dimension not greater than 3 feet (915 mm) and having wall and ceiling surfaces of gypsum board.
 
3. Bathrooms not more than 55 square feet (5.1 m2) in area.
 
4. Garages; carports; exterior porches; unheated entry areas, such as mud rooms, that are adjacent to an exterior door; and similar areas.
[Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 23-23-104, § 51-51-2904, filed 11/15/23, effective 3/16/24; WSR 20-12-027, § 51-51-2904, filed 5/27/20, effective 7/1/20.]
Site Contents
Selected content listed in alphabetical order under each group