HTML has links - PDF has Authentication
51-11C-407053  <<  51-11C-407054 >>   51-11C-407055

PDFWAC 51-11C-407054

Table C407.5.1(5)Number of chillers.

Table C407.5.1(5)
Number of Chillers
Total Chiller Plant Capacity
Number of Chillers
≤ 300 tons
1
˃ 300 tons, < 600 tons
2, sized equally
≥ 600 tons
2 minimum, with chillers added so that no chiller is larger than 800 tons, all sized equally
For SI:
1 ton = 3517 W.
[Statutory Authority: RCW 19.27A.025, 19.27A.160, and 19.27.074. WSR 16-03-072, § 51-11C-407054, filed 1/19/16, effective 7/1/16. Statutory Authority: RCW 19.27A.020, 19.27A.025 and chapters 19.27 and 34.05 RCW. WSR 13-04-056, § 51-11C-407054, filed 2/1/13, effective 7/1/13.]
Site Contents
Selected content listed in alphabetical order under each group