| | | Minimum Efficiency | |
Equipment Type | Size Category (Input) | Subcategory or Rating Condition | | | Test Procedurea |
PTAC (cooling mode) new construction | All Capacities | 95°F db outdoor air | | 14.0 - (0.300 × Cap/1000) EER | AHRI 310/380 |
PTAC (cooling mode) replacementsb | All Capacities | 95°F db outdoor air | | 10.9 - (0.213 × Cap/1000) EER | |
PTHP (cooling mode) new construction | All Capacities | 95°F db outdoor air | | 14.0 - (0.300 × Cap/1000) EER | |
PTHP (cooling mode) replacementsb | All Capacities | 95°F db outdoor air | | 10.8 - (0.213 × Cap/1000) EER | |
PTHP (heating mode) new construction | All Capacities | — | | 3.7 - (0.052 × Cap/1000) COP | |
PTHP (heating mode) replacementsb | All Capacities | — | | 2.9 - (0.026 × Cap/1000) COP | |
SPVAC (cooling mode) | < 65,000 Btu/h | 95°F db/75°F wb outdoor air | | 11.0 EER | AHRI 390 |
| ≥ 65,000 Btu/h and < 135,000 Btu/h | 95°F db/75°F wb outdoor air | | 10.0 EER | |
| ≥ 135,000 Btu/h and < 240,000 Btu/h | 95°F db/75°F wb outdoor air | | 10.0 EER | |
SPVHP (cooling mode) | < 65,000 Btu/h | 95°F db/75°F wb outdoor air | | 11.0 EER | |
| ≥ 65,000 Btu/h and < 135,000 Btu/h | 95°F db/75°F wb outdoor air | | 10.0 EER | |
| ≥ 135,000 Btu/h and < 240,000 Btu/h | 95°F db/75°F wb outdoor air | | 10.0 EER | |
SPVHP (heating mode) | <65,000 Btu/h | 47°F db/43°F wb outdoor air | | 3.3 COP | AHRI 390 |
| ≥ 65,000 Btu/h and < 135,000 Btu/h | 47°F db/43°F wb outdoor air | | 3.0 COP | |
| ≥ 135,000 Btu/h and < 240,000 Btu/h | 47°F db/43°F wb outdoor air | | 3.0 COP | |
Room air conditioners, with louvered sides | < 6,000 Btu/h | — | | 11.0 CEER | ANSI/AHA-MRAC-1 |
| ≥ 6,000 Btu/h and < 8,000 Btu/h | — | | 11.0 CEER | |
| ≥ 8,000 Btu/h and < 14,000 Btu/h | — | | 10.9 CEER | |
| ≥ 14,000 Btu/h and < 20,000 Btu/h | — | | 10.7 CEER | |
| ≥ 20,000 Btu/h and < 25,000 Btu/h | — | | 9.4 CEER | |
| ≥ 25,000 Btu/h | — | | 9.0 CEER | |
Room air conditioners, without louvered sides | < 6,000 Btu/h | — | | 10.0 CEER | |
| ≥ 6,000 Btu/h and < 8,000 Btu/h | — | | 10.0 CEER | |
| ≥ 8,000 Btu/h and < 11,000 Btu/h | — | | 9.6 CEER | |
| ≥ 11,000 Btu/h and < 14,000 Btu/h | — | | 9.5 CEER | |
| ≥ 14,000 Btu/h and < 20,000 Btu/h | — | | 9.3 CEER | |
| ≥ 20,000 Btu/h | — | | 9.4 CEER | |
Room air-conditioner heat pumps with louvered sides | < 20,000 Btu/h | — | | 9.8 CEER | |
| ≥ 20,000 Btu/h | — | | 9.3 CEER | |
Room air-conditioner heat pumps without louvered sides | < 14,000 Btu/h | — | | 9.3 CEER | |
| ≥ 14,000 Btu/h | — | | 8.7 CEER | |
Room air conditioner casement only | All capacities | — | | 9.5 CEER | |
Room air conditioner casement-slider | All capacities | — | | 10.4 CEER | |