Section C402.1.2Equipment buildings.

C402.1.2Equipment buildings. Buildings that comply with all of the following shall be exempt from the building thermal envelope provisions of this code:
1. Are separate buildings with floor area no more than 500 square feet (50 m2).
2. Are intended to house electronic equipment with installed equipment power totaling at least 7 watts per square foot (75 W/m2) and not intended for human occupancy.
3. Have a heating system capacity not greater than 17,000 Btu/hr (5 kW) and a heating thermostat set point that is restricted to not more than 50°F (10°C).
4. Have an average wall and roof U-factor less than 0.200.
[Statutory Authority: RCW 19.27A.025, 19.27A.160, and 19.27.074. WSR 16-03-072, § 51-11C-40212, filed 1/19/16, effective 7/1/16. Statutory Authority: RCW 19.27A.020, 19.27A.025 and chapters 19.27 and 34.05 RCW. WSR 13-04-056, § 51-11C-40212, filed 2/1/13, effective 7/1/13.]