Owners and operators must monitor underground piping for leaks using the methods, or combination of methods, of release detection specified in this section.
(1)
Piping requiring secondary containment. Underground piping requiring secondary containment under WAC
173-360A-0310 (5)(a) must be monitored for leaks as follows.
(a)
Pressurized piping. Underground piping conveying regulated substances under pressure must be equipped with an automatic line leak detector (WAC
173-360A-0640) and monitored for leaks at least every thirty days using interstitial monitoring (WAC
173-360A-0655).
(b)
Suction piping. Underground piping conveying regulated substances under suction, except as provided under WAC
173-360A-0600 (1)(b), must be monitored for leaks at least every thirty days using interstitial monitoring (WAC
173-360A-0655).
(2)
Piping not requiring secondary containment. Except as provided for previously deferred UST systems under subsection (3) of this section, underground piping not requiring secondary containment under WAC
173-360A-0310 (5)(a) must be monitored for leaks as follows.
(a) Pressurized piping. Underground piping conveying regulated substances under pressure must be:
(i) Equipped with an automatic line leak detector (WAC
173-360A-0640); and
(ii) Monitored for leaks at least annually using line tightness testing (WAC
173-360A-0650) or every thirty days using one of the following methods, or combination of methods, of release detection:
(A) Monthly automatic electronic line leak detection (WAC
173-360A-0645);
(B) Interstitial monitoring (WAC
173-360A-0655). This method may be used only if the piping is secondarily contained and meets the performance standards in WAC
173-360A-0310 (5)(c);
(b)
Suction piping. Underground piping conveying regulated substances under suction, except as provided under WAC
173-360A-0600 (1)(b), must be monitored for leaks at least every three years using line tightness testing (WAC
173-360A-0650) or at least every thirty days using one of the following methods of release detection:
(i) Interstitial monitoring (WAC
173-360A-0655). This method may be used only if the piping is secondarily contained and meets the performance standards in WAC
173-360A-0310 (5)(c);
(iv) Statistical inventory reconciliation (WAC
173-360A-0670); or
(3)
Additional methods for certain previously deferred UST systems. Underground piping not requiring secondary containment under WAC
173-360A-0310 (5)(a) associated with field-constructed tanks with a capacity greater than fifty thousand gallons or airport hydrant systems must be monitored for leaks in accordance with subsection (2) of this section or using one of the following methods, or combination of methods, of release detection:
(a) Line tightness testing (WAC
173-360A-0650) performed semiannually or annually, except the method must be able to detect the leak rate specified in Table 0615-1. Piping segment volumes greater than or equal to one hundred thousand gallons not capable of meeting the maximum 3.0 gallon per hour leak rate for the semiannual test may be tested at a leak rate up to 6.0 gallons per hour according to the schedule in Table 0615-2;
Table 0615-1: Maximum Leak Detection Rate per Test Section Volume
Test Section Volume (Gallons) | Semiannual Test - Leak Detection Rate Not To Exceed (Gallons Per Hour) | Annual Test - Leak Detection Rate Not To Exceed (Gallons Per Hour) |
< 50,000 | 1.0 | 0.5 |
≥ 50,000 to < 75,000 | 1.5 | 0.75 |
≥ 75,000 to < 100,000 | 2.0 | 1.0 |
≥ 100,000 | 3.0 | 1.5 |
Table 0615-2: Phase-In for Piping Segments ≥ 100,000 Gallons in Volume
Test | Time Frame | Leak Detection Rate |
First test | Not later than October 1, 2021 | May use up to 6.0 gallons per hour leak rate |
Second test | Between October 1, 2021, and October 1, 2024 | May use up to 6.0 gallons per hour leak rate |
Third test | Between October 1, 2024, and October 1, 2025 | Must use 3.0 gallons per hour leak rate |
Subsequent tests | After October 1, 2025 | Begin using semiannual or annual line testing according to Table 0615-1 |
(b) Vapor monitoring (WAC
173-360A-0660) performed at least every two years, except the method must use a tracer compound and be able to detect a 0.1 gallon per hour leak rate;
(c) Combination of inventory control (WAC
173-360A-0620) performed at least every thirty days, except the method must be able to detect a leak of at least 0.5 percent of flow-through and be performed in accordance with Department of Defense Instruction 4140.25, Air Transport Association Airport Fuel Facility Operations and Maintenance Guidance Manual, or equivalent procedures, and either:
(i) Line tightness testing (WAC
173-360A-0650) performed at least every two years, except the method must be performed in accordance with (a) of this subsection using the leak rates for the semiannual test in Table 0615-1;
(ii) Vapor monitoring (WAC
173-360A-0660) performed at least every thirty days; or
(iii) Groundwater monitoring (WAC
173-360A-0665) performed at least every thirty days; or
(d) Other release detection methods (WAC
173-360A-0675), except owners and operators must demonstrate the method can detect a leak as effectively as any of the methods allowed in (a) through (c) of this subsection and the department must approve the use of the method. In comparing methods, the department will consider the size of release that can be detected and the frequency and reliability of detection.